service condition
●Environmental temperature: max +40°C, min -15°C (under special processes, may reach -45°C)
●Environmental humidity: daily average <95%; monthly average ≤90%;
●Altitude: below 1000 m;
●Seismic resistance: seismic intensity not exceeding 8 degrees;
●Ambient air free from corrosive or flammable gases, water vapor, or significant pollutants;
●Free from severe contamination and frequent intense vibrations; design withstands harsh conditions meeting Class 1
requirements;
●Under normal environmental conditions exceeding those specified in GB 3906, agreement between the user
and manufacturer is required.
Note: ①Electric heater activation is recommended when relative humidity exceeds 70%. ②For locations above 1000 m altitude, follow JB/Z102-71 regulations.
Recommended products
Recommended products